JTEC UL 489 Series 10kA Miniature Circuit Breakers |
|
|
|
Technical Data |
|
| Current ratings (A) | 0.2, 0.5, 1, 1.6, 2, 3, 4, 5, 6, 7, 8, 9, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40, 50, 60, 63 (special current ratings available on request) |
| Number of poles |
1, 2, 3, 4, 1+N and 3+N |
| Trip curves to EN 60898 | B, C, K and D |
| Rated voltage (V) | 230/400 (EN 60898); 480Y277 VAC (UL 489, upto 32A) 240 VAC (UL 489, upto 63A) |
| Rated frequency (Hz) | 50/60 |
| Short circuit capacity EN 60898 (kA) | 10 |
| European energy limiting class to EN 60898 | 3, B and C 0.2A - 40A |
| UL interrupt rating (kA) | 10kA |
| Electrical life | 6000 cycles on/off |
| Mechanical life | 100.000 cycles on/off |
| Protection degree | IP 20 at front |
| Ambient temperature range | -25°C to 60°C |
| Operational position | In any plane |
| Compliance standards | UL489 / UL489A, EN 60898 /EN 60947-2 |
| Vibration resistance | 3g (8-50Hz) |
| Resistance to thermal shocks | 140°C |
| Connectable conductor cross sections |
AWG 12 (min.) AWG 3 (max.) |
| Tightening torque | 13lb/in (min.) 17.5lb/in (max.) |
| Download JTEC 489 PDF (695KB) |
|
Techna's Jtec 489 range is UL 489 listed (File E255530). Available in trip curves B (quick), C (medium), K (motor) and D (long delay) in current ratings from 0.2 to 63A, and all available in 1, 2, 3 or 4 poles, Jtec 489 10kA MCBs offer maximum
performance at excellent prices. Benefits for Engineers and Designers A. Jtec 489 is UL Listed as a branch circuit breaker and is therefore able to be used to protect a branch circuit without a backup device. Many applications and other UL standards insist upon the use of a branch circuit breaker (as opposed to a supplementary protector). If you fit the Jtec 489 you're covered! D. Jtec 489 is also available UL Listed up to 10kA in 250VDC ratings. E. Jtec 489 also meets European standard EN60898 and EN60947-2 for circuit breakers and is CE marked, ideal for manufacturers seeking to stock a single product to use for global production requirements. F. Jtec 489 has a full range of accessories. Auxiliary contacts with both changeover and signal circuits - meaning you can remotely monitor the state of the breaker (ON or OFF) and you can tell whether the breaker was manually switched off or has tripped due to a circuit fault. Shunt trip modules enable remote shutdown of the device. The under voltage release modules automatically switch off the breaker in the event of a power failure, thereby protecting against an unexpected machine start-up when mains power is restored.
Uniquely the N-pole (Neutral Pole) add on means you can convert a 3 pole breaker into a 3 pole + switched neutral device with one shared component, so you do not need to stock 4 pole devices, making inventory savings. C. Lockoff adaptors are available to enable breakers to be padlocked on (to prevent manual turn off), or locked off, for example by service engineers working on the system. D. The breaker features a trip indicator window to show if the breaker has tripped even if the handle has been inadvertently prevented from movement. This saves a lot of time by enabling quick identification of a tripped circuit when an engineer is on site. |